Martindale EasyPAT Manual Tester

Martindale EPAT1600 EasyPAT Manual Tester

MARTINDALE EPAT1600

£411.75 ex. vat £494.10 inc. vat

Usually ships in 5 working days

Martindale EPAT1600 EasyPAT Manual Tester MARTINDALE EPAT1600

Details

MARTINDALE EPAT1600
Martindale EasyPAT Manual PAT Tester


The EasyPAT 1600 is a legal minimum tester suitable for high speed, low cost testing.

Does both mandatory tests and has a built-in fuse test 25A, 8A and 100mA (for computers etc.) earth bond tests selectable with a simple rocker switch Incorporates an extension lead tester to test IEC leads (can also be used to test 110V extension leads with a MAREX331 adaptor) Tests both 110V and 240V appliances for 240V supply

Technical Specification

ELECTRICAL
Supply Voltage: 230V?10% 50/60Hz
Power Consumption: 10/220VA
EARTH CONTINUITY TEST (8A & 25A)
Test Voltage: 6V AC nominal with no load
Test Current: 25A AC nom @ 0.1O (25A), 8A AC nom @
0.1O (8A)
Display Range: 0 - 1.99O
Accuracy of Indication: ?10% of reading ?2 digits

EARTH CONTINUITY TEST (100MA)
Test Voltage: 130mV DC nominal open circuit
Test Current: 100mA DC nominal constant current
Range: 0 - 1.99O
Accuracy of Indication: ?10% of reading ?2 digit

INSULATION TEST
Test Voltage: 500V DC -0% +20% at 0.5MO
Short Circuit Current: 1.5mA DC nominal
Display Range: 0 - 19.9MO
Accuracy Of Indication: ?5% of reading ?1 digit

FUSE TEST
Test Voltage: 6V AC nominal
Over range threshold: 10kO nominal
Zero range threshold: 800kO nominal

LEADS
Mains: 1.7M fixed lead, with a 13A moulded plug
Earth Continuity: 3M long, detachable lead, heavy duty
crocodile/alligator clip.
230V IEC Adaptor: 13A BS1363 plug to IEC320 connector,
230mm long.

SOCKETS
Mains: 230V 13A to BS 1363
110V 16A to BS4343
Leadtest: IEC320

LAMPS
Over Temperature: Red LED which illuminates when the
temperature limit for the instrument has been exceeded.
LED extinguishes when unit cools.
Lamp 1/ Lamp 2: Red LEDs which illuminate to indicate lead
polarity for extension lead test facility.

FUSES
Plug: 13A 1HBC (Ceramic)
Internal: 3.15A (F) 5x20mm, HBC (Ceramic)
Internal fuse is not user replaceable.
Safety
EMC: Meets BS EN 50081-1
BS EN 50082-1
LVD: Meets BS EN 61010-1

MECHANICAL SPECIFICATION - CASE
Size: 330x263x144mm
Material: ABS/Polycarbonate
Colour: Yellow/Black
Weight: 4kg nominal

ENVIRONMENTAL SPECIFICATION - TEMPERATURE
Operating: 0 ?C to 35?C
Storage: -10 ?C to 50?C
This instrument has been designed to be used in a clean dry environment.